With regard to output, this hardware has 4 sources (T0, T1M, T2, T3M). The aggregate current of test outputs per module are 2.8 Amps at 40 degrees Celsius and 0.55 Amps at 55 degrees Celsius. It has a pulse period of 144 milliseconds and a maximum current (when used to control muting lamp) of 25 milliAmps; minimum current when used to control muting lamp is 5 milliAmps.
Additional technical specifications for the 1734-IB8S include a maximum residual voltage of 0.3 Volts and a maximum output leakage current of 0.1 miliAmps. This module is equipped with short circuit protection and has a maximum POINTBus current of 110 milliAmps. Maximum power dissipation is 3.0 Watts and maximum thermal dissipation is 10.25 British Thermal Units (BTU) per hour; typical power dissipation is 2.25 Watts and it has an isolation voltage of 50 Volts (continuous) with basic insolation type. The test outputs for pilot duty rating are not rated. The 1734-IB8S has an approximate weight of 62.4 grams, or 2.2 ounces and approximate dimensions of 77 x 25 x 55 millimeters, or 3.03 x 0.98 x 2.17 inches.